Contact
Isolated 3D TITANUS PRO·SENS /net in front of a high-bay warehouse - a typical use case

TITANUS PRO·SENS ®­/net

TITANUS­ PRO·SENS ®/net for increased performance requirements

The TITANUS­ PRO·SENS ®/net is the ideal solution for room monitoring of up to two areas of 3,000 square meters each as well as for applications in the mobility industry that require an extended range of features. The aspirating smoke detector supports staged alarming, has an input for day/night switching and offers an optional Ethernet connection. It is also optionally available for use in operating temperature ranges of up to -40°C to +60°C and as a SILENT variant.

Front view of a TITANUS PRO.SENS/net aspirating smoke detector

FACTS

TITANUS­ PRO·SENS ®/net at a glance

For large monitoring areas and extreme conditions

  • Up to 2 x 3,000 m² monitoring area
  • Response sensitivity from 0.005% LT/m
  • Depending on type, up to 2 x 3 alarm thresholds
  • Two-message dependency type A
  • Input for day/night switching
  • LOGIC·SENS ® fire pattern recognition
  • Optionally with Ethernet (SNMP) connection, 2GB data logger
  • Operating temperature range from -40°C to +60°C
  • SILENT variant from 23 dB(A) sound pressure level

BENEFITS

TITANUS­ PRO·SENS ®/net offers safety for your application

Fire in a circle as an icon

Earliest possible fire detection

Early fire detection for the greatest possible time advantage in the event of a fire.

Crossed-out bell as an icon

False alarm immunity

LOGIC·SENS ® fire pattern recognition protects against false alarms.

A diamant as an icon

Aesthetic and discreet

Virtually invisible fire detection, barely audible in the SILENT version.

Icon universal globe

Robust and temperature-resistant

Operation within deep-freeze areas possible.

Stacked squares

Modular

Extensive range of accessories for optimum adaptation to the requirements of the application.

An icon in the shape of a cross made of arrows

Scalable

Monitor two separate monitoring areas or implement a two-message dependency.

Icon screen with a heart

Staggered alerting

Supports a tiered alarm concept with up to two 3-level alarms.

Topology star as an icon

Networked

Integrates with building management systems via Ethernet / SNMP.

An icon of a power button

Protection of operational readiness

Early detection of breaks and blockages in the pipe system using PIPE·GUARD.

FEATURES

Equipment and application features for your application

TITANUS PRO.SENS/net sensitively detects smoke development

Sensitivity

The pipe system to the TITANUS PRO.SENS/net aspirating smoke detector is continuously checked by the patented PIPE-GUARD system

PIPE·GUARD

To avoid false alarms, TITANUS PRO.SENS/net uses the patented LOGIC∙SENS signal processing system

LOGIC·SENS

An alarm is only confirmed when at least two TITANUS PRO.SENS/net aspirating smoke detectors are triggered (two-detector dependency)

Dual detection dependency

TITANUS PRO.SENS/net has three alarm levels

Three alarm stages

TITANUS PRO.SENS/net has an optional wide ambient temperature range (from -40 to + 60° C) and is therefore suitable for installation in deep-freeze areas

Deep-freeze

TITANUS PRO.SENS/net can be connected to hazard and building management systems via Ethernet and SNMP

Ethernet

The particularly quiet SILENT version from 23 dB (A) is optionally available for TITANUS PRO.SENS/net

SILENT

DOWNLOAD

TITANUS­ PRO·SENS ®/net facts and figures

You can find more information about TITANUS PRO·SENS ®/net­ in our data sheet.

M. Dorsch: Director Market Solution Management

Find the optimal aspirating smoke detector for your application

I will be happy to support you with my expertise.

Artur Hulm

Head of Market Management

+49.511.97383-0